Author: ABBdriveX

AQ: DC link fault in 3 phase frequency inverter

Question:
Our one frequency inverter which drives 0.37 KW 400 V dosing pump motor intermittently (once in a month or once in two months) shows DC link fault and the speed is reduced to zero. This motor used to do changeover weakly. Pump NO: 1 never has such problem, pump NO: 2 only have this problem. We checked the motor found OK, checked the control circuit found ok, replaced with same new inverter still the same problem comes. We thought of incoming power supply problem so we swapped power supply cable from motor 1-2 but still the DC link fault comes in pump NO: 2. Then some of our experts said it is because the inductor is connected in the circuit, once remove the inductor this fault will not come again. But after removal of the inductor also same problem comes. From the previous history of work orders we found that this motor is a rewound motor, before rewinding there was no fault history at all. This motor is running always perfectly without any faults in manual control. Fault comes only in automatic control.
Could you please tell me what is the real problem?
Is it because of rewinding of the motor; winding geometry might have changed that affects the frequency inverter?
If this is the problem then why this fault is not coming whenever it is in service? (It waits for 1month or two months some time the fault comes in a weak also)
Is that the inverter will cause any problem because the inductor is in disconnected condition?
What is exactly the DC link fault and what are the reasons it can come in the inverter?
Why the DC link fault comes in when it is in automatic operation only?

Answer:
Have you compared the good unit to the bad unit?
Could there be any mechanical issues loading the motor?
Check that the current level on the bad motor is the same as the good motor.
It sounds as if the rewind data is not correct and the motor is taking high current. If the rewind data is correct the core loss may be high.

The procedures you have gone through would indicate that the motor is the issue. My advice would be to go to the OEM and purchase a new motor or if it is a standard motor your regular supplier should be able to supply them. It could even be beneficial to purchase two new motors and keep the existing good one as a spare.

AQ: Can soft starters create shaft voltages similar to VFD’s?

We recently evaluated a 500 HP 4 pole motor on a pump application. The motor is started with a soft starter. Upon examination of the bearings we discovered fluting inside both the variable frequency drive and opposite drive end bearings.
If it were shaft currents, especially on a pump, the fluting would be typically on the non-drive end only, excess shaft current would be drained through the apparatus attached to the drive end shaft. We would more likely suspect a vibration issue with the assembly while inactive. What is base condition for the pump? Is it on a stable foundation or is it mobile? If mobile, and transported you need to “lock” the shaft to avoid axial or radial motion.
PAM winding is still a feasible alternative to VFD where simply two or three discrete speeds are necessary without the need for servo-like control, mostly for high power applications as was mentioned above. Only several extra leads and contactors but no nasty harmonics, reduction of insulation life and no additional variable frequency drive that takes space & is not cheap to buy or maintain, might become obsolete and most likely will not last as long as the motor.
Note that some shaft couplers are insulating; and therefore, won’t drain shaft voltages.

However, all of the soft starters that I have used are line (mains) frequency phase angle modulating. Hence they act as three phase variacs (variable autotransformers). I have not run across any stray voltage problems with these units. However, some soft starters modulate only two of the three phases. I don’t know what this will cause.

Regarding VFD’s, three steps are needed to protect the motor: 1) High enough winding voltage withstand voltage (dielectric strength), 2) Adequate thermal capability to counter the extra (5% or so) winding heading due to the harmonics, and 3) protecting the bearings from developed stray voltage (grounding, bypassing or insulating).

A soft starter is in the circuit for so short a time, it is not likely that the fluting is coming from the drive. My logic is that fluting is a low current long time event. Bearing damage that could occur from the very short and very infrequent duration of starting would have to be a very high energy (for that short time), and would more likely be pitting.

In evaluating all possible sources:
There have been instances where the external current is coming from the plant piping. This would be eliminated by insulating the piping from the pump (if a flanged connection, use an insulative gasket [no metal fibers or rims], and plastic sleeves & washers for the bolt set).

Other motor related sources: the API motor specs say to insulate one end where the shaft voltage exceeds 500 mV. This can be done many ways, and usually done on the non drive end. (Have you measured the shaft voltage?)

I am not a big fan of shaft grounding brushes, and grounding the plant piping may not be enough. Brush contact is not reliable, and may not drain all the current (same for grounding the pipe).

Anecdotally: an electric utilitie had system grounding problems that elevated the potential of “ground” in a dairy. The path to lowest potential was through the cow to the milking machine to “ground”. Milk production went down, it took a while for the farmer to get the utility to check their system. Finally they did, fixed the transmission system grounding, and the problem disappeared.

AQ: Cable length between VFD and Motor | Iacdrive

The dU/dt at the output of the variable frequency drive combined with the motor cable length will result in very high voltage peaks at the motor terminals. This is a concern for the isolation in motors not designed to be driven by VFDs.
On the other hand the maximum motor cable length depends also on the switching frequency used due to the charging effect of the motor cable capacitance (this is a limitation on the variable frequency drive side, not on the motor isolation).
The dU/dt at motor terminals normally is very different from the dU/dt that you can calculate from IGBT and its driving characteristics (turn on time, gate resistor, etc) at variable frequency drive terminals. As the cable acts like a distributed LC impedance, the dU/dt calculation on VFD terminals will give you very high values that can be apparently dangerous, but in practice, will not happen at motor terminals.

For long cables, the combination of cable impedance, high frequency input impedance of motor and VFD switching frequency can lead to reflection of voltage pulses that gives origin to large voltage overshoots on motor terminals. The problem increases as increasing switching frequency because the time between voltage pulses will be smaller, so, a voltage pulse reaching the motor will add to the pulse being reflected. This “double pulsing” can results in extreme voltage overshoot and dU/dt that will result in motor insulation failures. For the variable frequency drives side the increasing switching frequency will be a problem (besides power losses) if you have a big capacitor filter at converter output, that can lead to high current pulses at inverter side.

The determination of the resulting dU/dt at motor terminals from the dU/dt at VFD drive terminals is very difficult if you try to use simulations. For this task you’ll need the high frequency parameters of cables (that also depends on installation details) and motor, that will not be available from standard datasheets and are very difficult to obtain from measurements. In practice almost all VFD manufacturers make extensive measurements and establish some criteria in order to orient applications. The approach is to determine if it is necessary or not to have an output filter for a known application (cable length).

For instance, a common specification is:

For cable lengths up to 100 meters (and motor suitable for variable frequency drive applications) it is not necessary a filter; for lengths from 100 to 200 meters, a series reactance can be used; for greater lengths it is necessary an LC filter at VFD terminals. The limit lengths can be different from different manufacturers and voltage levels (LV/MV). Iacdrive, for instance, can give complete orientation for application of its drives considering the needed cable length for the application.

AQ: Variable frequency drive Vector control VS V/F control

As far as I know all variable frequency drives with vector control can also be run with just V/F control.

A drive in vector control mode has several tuning parameters to increase or decrease motor performance. With factory default parameters a VFD in vector mode will have higher performance than a drive in V/F mode. Sort of like a “sport or racing” computer option in a modern automobile.

Depending on the application using vector control can use a lot more power. If you have a rapidly surging load the vector may be really struggling to keep the speed constant while a variable frequency drive in V/F mode never notices the speed change. If the application has a steady mid-range speed and load or has a slow rate of change a vector and V/F may be very close in amp draw.

If you have an application where you need the vector for starting or stopping quickly but you are using a lot of current at speed you can change vector parameters to reduce the current. In some applications it is cheaper to oversize a V/F drive to get starting or stopping torque if you don’t need precise speed control.
I accept the fact that, in the practice, V/f is considered by many the better choice for fan loads, but I see few reasons why V/f approach could result in better efficiency.

One reason could be that, since it doesn’t try to regulate anything, practically it can’t oscillate due to weak stability, although oscillations may still occur (I’ve seen a heavily vibrating torque measurement on a fan driven by a V/f variable frequency drive).
Another could be that, while non-linear V/f curves (suitable to non-linear loads as fans) are quite common, the same is not done for the flux reference (magnitude) in vector control.
And, of course, the few parameters of a V/f control are far easier to tune than a vector scheme (which companies don’t really share).

However, one interesting thing that can be done with vector control is, for slow dynamics applications, to automatically tune the flux reference to achieve a minimum loss control during the control operation. I don’t think this would be possible with V/f.

AQ: Synchronous motors VS induction motors

1- Synchronous motors generally offer more efficiency than induction ones, and hence in higher ratings (about 5000 hp and higher) they may be more cost effective considering Life Cycle Costs. The exact size of preference to switch to Synchronous shall be determined based on LCC analysis of specific application.
2- A Large reciprocating compressor is a highly variable load and a synchronous motor will keep its speed in this situation while the induction motor would respond with fluctuating speed.
3- Based on API 618 (with reference to IEC and NEMA), a synchronous motor used for reciprocating compressor may tolerate 66% variation in current, while an induction motor is allowed to have only 40% variation in current which in larger compressors may be exceeded (because of variable load).Also Higher efficiency induction motors with less slip, cause more current variations and are prohibited.

Synchronous motors are characterized by limited starting torque, the ability to actively control power factor and less current in-rush than the induction motor. The synchronous motor also requires active matching of torque demand with motor output. Synchronous motors started “across-the–line” also produce oscillatory torques at the twice slip frequency during acceleration (i.e., starting at 120 Hz and decreasing to 0 Hz at full speed). These torques generally require additional transient torsional analysis because of the potential for damage.
Synchronous motors are usually advantageous on slow speed applications (e.g., low speed reciprocating compressors operating from 200-400 RPM) and also on machines larger than about 10,000 to 15,000 HP.  With both motor types, it is important to match the compressor torque versus speed requirements with motor torque versus speed capabilities as discussed in Sections 6.0 and 7.0. Both induction and synchronous motor types can be coupled with a VFD for variable speed operation.

If the motor is being driven by a variable frequency drive with sophisticated drive algorithms, i.e. controllers that can track the load torque variations, then both the efficiency and transient stability problems can be solved together.

The other significant thing is the starting problem. The transient load torque is also present at starting so the motor has to be able to accelerate through the load transients and be capable of starting when the compressor is sitting at the highest load.

AQ: What’s the difference of variable frequency drive and soft starter

variable frequency drives are two different purpose products. VFD is for AC motor speed control, it’s not only change the output voltage but also change the frequency; Soft starter is a regulator actually for motor starting, just changing the output voltage. Variable frequency drive has all the features of soft starters, but the price is much more expensive than the soft starter and the structure is much more complex.

Variable frequency drive is converting power supply (single phase VFD and three-phase variable frequency drive.

Soft starter is a set of motor soft start/stop, light-load energy saving and various protection functions devices to control motors.

Soft starter uses three opposite parallel thyristors as regulator, plug it into the power source and motor stator.  When using soft starter to start the motor, the thyristor output voltage increases gradually, and the motor accelerates gradually until the thyristor is turned on completely. The motor operates at rated voltage to achieve a smooth start, reduce starting current and avoid start overcurrent trip. When the motor reaches rated RPM, the startup process is completed, the soft starter uses bypass contactor to replace thyristor to provide rated voltage to the motor, in order to reduce the thyristor heat loss, extend the soft starter service life and improve efficiency, also avoid harmonic pollution to the power grid.

AQ: Motor Rotor Bar issue in Current Signature Analysis

The condition of the rotor bars will determine how much torque your motors will deliver. As a person who has been in the electric motor repair business all my life it is something I constantly check. Normally when you talk about rotor bar health it refers to open rotor bars however I have found that in aluminium die-cast rotors there can be voids in the end-rings. Todays vibration equipment and your CSA equipment is so sensitive that it will pick up these voids. In a repair shop environment and with a motor with a good stator winding it is relatively simple to check for open rotor bars. if at all possible we will check for open rotor bars before we take a motor apart by performing a single phase rotor test. You apply approximately 20% of line voltage to two phases of the motor. Rotate the rotor through 360 degrees and monitor the current. If the current is steady the rotor is in good health. If you have one or more open rotor bars the current will drop as the open bars pass the energized part of the stator. A 10% swing would indicate open rotor bars.
Just in case there is a second cage in the rotor you can also put a voltmeter across one of the energized phases and the open phase. Just like the current, the voltage should stay steady.
When a motor is developing open rotor bars it will become noisy on start up. Noisier with each bar that becomes open. It can sound like a cement mixer or as if there is no lubrication in the bearings.

I have no idea what a rotor bar health index is. I would assume that it is a severity level that has been developed by the people who manufacture your test equipment.

Neither am i familiar with the Motor Current Signature Analysis. We use a surge tester which has an attachment for checking rotors but I don’t put much faith in it.

Open rotors can be a nightmare for electric motor repair facilities. Open rotor bars are not always visible and can be very difficult to detect. Our core tester has clamps that allow us to induce a low voltage and high current into the rotor cage but it is not conclusive. We could use a growler to energize the rotor and throw iron filings over the core. On a big rotor it takes a bit of time and customers don’t like paying for it, especially when you don’t find any problems.

If your motors are die-cast aluminium and they are starting up every day without struggling to get up to speed and they are not noisy during start up, your equipment might be picking up voids in the aluminium.
If you have copper or copper aloy rotors with brazed end-rings and I might suggest that you be concerned. Once you get one open rotor bar it only gets worse as time goes by.

AQ: What’s PG card in variable frequency drive?

PG is short for Pulse Generator, generally it is used for measuring rotational speed. The most common PG card is optical encoder.
PG card is a part of vector variable frequency drive, to convert the encoder different form signals to suitable for the controller, like: electrical level conversion, analog digital conversion, optical isolation, etc.
Vector control variable frequency drive is a high-performance drive which can be comparable with DC converter.
In the vector control, it requires a motor speed feedback to the variable frequency inverter drive, this speed feedback is achieve by adding a rotary encoder (PG) to the motor, which means PG card feedback vector control VFD. In order to simplify the system, the feedback can be formed by operation of the inverter output signal, this control is called none PG card feedback vector control VFD, the performance has a slight gap than PG card feedback, but configuration is simple.

AQ: Motor testing and repairing

Are you having noticeable performance problems with these motors? The size and type of motor are critical as mentioned, a cast rotor with the right testing can pick up voids in the bar and resistance rings, not necessarily a problem as most mass produced cast bar rotors will have some sort of voids in the bars, and the motors are fine, the red flag comes up when using these black box tests, which picks up what appears to be a problem but is actually just a normal condition from the manufacturing process.

I have very little faith that any one test on an assembled motor, can tell the user everything about the condition of the internals, or health of the motor.

When you consider all the testing the health field can use, such as a full body scan, many times it leads to false alarms and more expensive testing.

I could ask a few dozen questions on the age, type, past testing, past history of the motors in question, but if you are basing the health or life expectancy of any motor by only the use of testing without a visual of the internals of a motor, those questions need to be addressed to the supplier of the testing equipment.

I believe in predictive maintenance, by vibration charting, insulation value testing, surge testing, all charted and plotted over time.

When you have insulation values at 100 megohms in March, and then 500 in July, it is likely the ambient conditions have effect on the readings. Dependent on the ambient conditions and area the motors are located, humidity in March is gone in July. So plotting the readings over time will give a plot to see if the trend is downward regardless, or it could be the readings in March are fairly constant, the readings in July are constant, but there is no downward plot of the insulation value.

When you get insulation values in March of 100 megohms, and again in July but the megger readings are now 60, then a user would want to decrease the time between testings, starting with say quarterly, once you develop a plot, if that plot changes downward, then it is time to test maybe even weekly as it may show some kind of insulation breakdown, or contaminates that would call for a visual inspection and possible cleaning/repair of the motor.

Same with plotting surge tests.

Same with plotting vibration testing.

But the answers to these questions where the test results are confusing at best, need to be addressed to the testing equipment provider.

I have yet to see any demonstration of a total motor health testing device, that did not have some caveat dependent on the speed or other design factors of particular motors.

Maybe these tests were not confusing prior to now, if so, I doubt two identical motors would fail/start to fail with the same exact type of problem.

Again I could ask a dozen questions such as are the motors new, is this the first time you have results that make no sense, and as much of the total history of the motors and testing programs you have in place.

When it comes to rotors, testing is critical, and often when problems are found with the motor, and all testing points to the rotor, often simply repairing the rotor will not resolve the problem.

In speaking with many engineers over several decades, a large manufacture of large electric motors, have decided once a rotor is identified as the problem, rebarring, or any single repair is usually unsuccessful, and their procedure is to scrap the rotor completely.

AQ: Soft starter VS variable frequency drive

Soft Starter reduces electric motor starting current to 2-4 times during motor start up, reduces the impact to power grid during motor start up, avoid the motor being burned out, and provide protection in motors running process.

Variable Frequency Drive allows the electric motor smooth start up, control startup current growing from zero to motor rated current, reduce impact to the power grid and avoid the motor being burned out, also provide protect in  motor running process. Besides these functions, the main function of variable frequency drive is adjusting the motor running speed according to actual operation conditions, to achieve energy saving effect.

So, from the function side, variable frequency drives are much better than soft starters.

One essential difference between a soft starter and a VFD in this regard is, that the VFD delivers “nearly” sinusoidal voltages (and currents) to the motor, which makes it possible to develop high starting torques during the acceleration, even higher than nominal full load torque, depending on the application, while a soft starter only supplies fractions of the basic waveform, which serves to reduce the current to the motor significantly, but still at the nominal frequency. This will reduce the available starting torque dramatically until the motor is up to around two-thirds of nominal speed, or maybe even higher.