Category: Blog

AQ: Circulating current in parallel transformers

When two transformers are in a parallel group, a transformer with a higher tap position will typically have a higher (LV side) no-load voltage than the other one with a lower tap position. These unequal no-load voltages (unequal tap positions) will cause a circulating current to flow through the parallel connected transformers. A transformer with higher no-load voltage (typically higher tap position) will produce circulating current, while a transformer with lower no-load voltage (typically lower tap position) will receive circulating current.

When load is connected on these two parallel transformers, the circulating current will remain the same, but now it will be superimposed on the load current in each transformer, i.e. for a transformer producing circulating current, this will be added to its load current, and for a transformer receiving circulating current, this will be subtracted from its load current.

Thus voltage control of parallel transformers with the circulating current method aims to minimize the circulating current while keeping the voltage at the target value.

In case of a parallel operation of transformers, the electric current carried by these transformers are inversely proportional to their internal impedance. Think of it as two parallel impedances in a simple circuit behind a voltage source, you will have equal currents through each impedance only if you have two identical impedances, in some cases as stated above, tapping could be a problem, the other one is the actual manufacturing tolerances which could diverge by almost 5-10%, if the transformers are manufactured by different suppliers or not within the same batch. So, the difference in current between the currents through these two impedances is basically the circulating current as it is not seen outside these parallel impedances.

The currents that are produces due to magnetic flux circulation in the core are called eddy currents and these eddy currents are responsible for core losses in transformer.
While the circulating currents are the zero sequence currents that may be produces due to following causes.
1- when there is three phase transformer the (3rd, 5th, 7th….) harmonic currents which are called zero sequence currents from all the three winding of three phase transformer add up and become considerable even in loaded conditions these currents have no path in Y/Y connection of transformer so a tertiary winding is provided co conduct these currents but in Y/d or D/y connection these currents circulate in delta winding.
2- Whenever there is unbalanced loading in transformer. In which with positive sequence, negative sequence and zero sequence currents are also produced which cause circulating currents.
3- When the transformer banks are used and the transformers have phase between them then circulating currents are produced between them, than transformers in the bank get loaded without being shearing the power to the load.

AQ: What is the Reactive Power?

For a “physical” interpretation, reactive current (power/KVA flow), in my opinion is best looked at from the perspective of a generator connected directly to an infinite bus (in LV generators this is the norm).

The generator when connected to the system, “see’s/feels” the parallel impedance combination of all other generators (circa 3 ohms each) with respect to ground – which basically parallel to equate to a zero impedance in terms of restriction to any current flow out of our generator.

Post initial synchronization, the system voltage prevents currents from flowing into or out of the generator due to pressure (voltage) balance of our generator matching that of the system voltage.

If you (as the generator operator), try to lift the generator voltage, the result will only be heaps of current output flowing into the system – but with no actual extra power generated!

This is due to the fact that to achieve the extra generator voltage setpoint you desired, the generator must send out enough current into the system impedance to create the back emf required to achieve the new desired generator terminal voltage setpoint.

But because the system impedance to ground is very low (as it actually is) – then despite the extra current sent out in that fruitless attempt, the generator is near impotent to make any substantial effect on raising the “system” voltage – “fruitless” current sent out.

In a DC sense you can equate this to a small DC generator trying to lift the voltage of a load system that has a zener diode installed across that system load.

Back to the AC world, ….that current sent out in the fruitless attempt to lift system voltage must flow through the parallel low impedance of the other connected generators (each of those working against you – lowering their own generator excitation, hell bent on keeping their own same old voltage set points), thwarting our futile attempt to achieve a raise in the system voltage.

All those generators, although collectively of low impedance, compose virtually no resistance, compared to their inductive reactance. Hence all our little generators current flow – in its futile attempt to lift system volts – is virtually purely inductive.

So we have heaps of current flowing out in our attempt to lift generator volts, but because the current is 90 degrees lagging the voltage, the only power imposed on the generator prime mover is that due to the resistance of the generator windings (circa 1% of the full load current rating – hence basically un-noticeable).

Hence the physical interpretation of VAR’s, is actually simply a look at the voltage balance perspective of an electricity network. It’s the collective attempt of many parallel-connected generators to influence the system voltage – either trying to raise the voltage at a particular node (positive VAR’s) or trying to reduce the voltage at a particular node (negative VAR’s flowing back through our generator due to our attempt to lower our generator setpoint – which “lets current in”).

Reactive Power is an electrical parameter that exist in a sinusoidal (AC circuits). It maybe zero or a certain magnitude. It maybe capacitive in nature or it maybe inductive nature. In the power triangle, it is the vertical power component (plus or minus / capacitive or reactive). It may be supplied from power sending end (grid or generator) on from the power receiving end (load). A capacitor bank connected on the grid provides capacitive reactive power. An inductor bank connected on the grid provides inductive reactive power. Both of them have magnitude. Reactive power also influences the between phase angle displacement between the voltage and the current. It is power but reactive power.

AQ: Is frequency inverter better than soft starter in motor control?

There are hundreds of applications for a frequency inverter. I use them on a pump to test pumps with voltages from 208-600VAC 3PH 50 and 60 HZ. You just have to size the frequency inverter to the largest 208 HP motor, so it can handle the current. Many people are installing them on pumps, fans and air compressors to get the energy savings of lowering the speed on the motor to maintain the pressure, temperature and flow. Frequency inverters also have the ability to ride through power dips, since the DC bus to store in a capacitor bank.

It is correct the frequency inverter will reduce the staring current of and induction Motor, but as all of you know that the motor have to drive a load the starting torque is related to starting current, also the main role of frequency inverter is to control the speed.
The starting current is related to the rotor conductor structure or classes because we can get direct starting currents within 1.5-4 times the full load depend on the squirrel cage design or construction.

The effect is, that at the reduced frequency during start, the full torque can still be developed at nominal current. As soon as the frequency hits the nominal slip frequency, the nominal torque will also be developed, at nominal full-load current. (The slip frequency is the nominal frequency multiplied by the full load slip percentage, i.e. around 2.5Hz for a 50Hz motor with a full load slip of 5%).

It really depends on the application. If you are only interested in starting current, then soft start is what you need.

AQ: Circuit Breakers tests

1- For small circuit breakers we can do the test of Magnetic protection behavior by using “Injection Current Apparatus”, and suppose the CB’s results were good, do you think it’s enough? I’m sure not, because by this apparatus we can inject the necessary current with a very low voltage value (5-15V), so, do you think that the arc will be the same if we have the same current but with “400V”?

2- The same question for “Short Circuit Tests”

Personally, I done the tests of many MCBs for different manufactures by using “Injection Current Apparatus”, and I saw the same tests in laboratory in France for the same MCBs by injection the same currents values with 230V or 400V depending on the CB, be sure, the results weren’t the same, we found some differences for Magnetic protection tests, and big differences for Short Circuit tests.

AQ: Why BLDC motors are noiseless compare to Induction motor?

If referring to the acoustic noise generated at or around the PWM frequency of the PWM frequency. There are more laminations in an induction machine. This may account for some of the difference.

I also don’t know what the relative power difference is between the BLDC and the induction machine. If it’s about a 5Hp BLDC and a 100Hp induction machine, then you can bet that the PWM frequency of the BLDC is likely above the audible range and the PWM frequency of the induction inverter is well within the audible range.

These are just a few reasons that you may find subtle differences between the two. There are many factors and more information is needed to really help understand your specific situation.
I also believe there are simply sophomoric and unprofessional answers. My statement is based on the general rule that there is greater surface area between laminations of squirrel cage induction machine then there are in BLDC machines. Of course, if you want to state that you have a thin lamination on a long stack length design for a BLDC then there may be an argument that such a motor design when compared to a typical induction machine of the same power has a similar surface-to-surface lamination area. It is these laminations moving due to eddy currents at the PWM frequency that causes the audible noise.

BLDC can come with very small inductance which requires a higher PWM frequency, if you compare both them with controller that may cause different.
If you build 2 motor using exact mechanical shapes and electrical parameter they should be very close. You can build 2 induction machines from 2 different vendors to same electrical spec and they will not sound the same.

AQ: System configuration of grounding

There are different types of system configuration for grounding like TT,IT,TN-C etc. How do we decide which configuration is suitable for the particular inverter (string or central). What are the factors that help us to decide the configurations?

One of the main concerns in a system is to avoid large low impedance ground loops.
These are created by the return signal path connected to the chassis (metal work) at multiple points. The large current loop allows noise currents to radiate H fields and hence couple into other electronics. The antenna effect will be proportional to loop area.

Single point grounding of the return path to chassis prevents this. However single point grounding conflicts with good RF practice where you want to ground to chassis at the sending and receiving ends of a signal path. There is therefore no universal best practice.

In my field, spacecraft, the standard practice has all primary power electronics galvanically isolated from the spacecraft chassis. Individual modules must maintain the isolation with transformer coupled DC/DC converters. The centre tap of each PSU secondary output is then single point grounded to the module metalwork. We talk about primary side and secondary side electronics where only secondary side is grounded to the metalwork.

Anything powered directly from the primary bus must be isolated with a maximum capacitance to chassis of 50nF to avoid excess HF loop currents forming.

In general it depends on country specific law and standards required by Power Supply Operators. From design point of view it all depends on which point of grid you are going to connect and what type of inverter is used.

AQ: Lighting control panel to distribution board

There are a couple of construction differences which may be present, depending on the style of “lighting control panel”.

First, a distribution board typically has poly-phase branch breakers with the intention of feeding either other sub-panels or large loads — such as a motor with a motor controller.

A lighting control panel will have mostly single-pole breakers with phase-to-neutral branch circuits feeding lighting circuitry. There is the added possibility of having either ‘smart’ breakers or integral contactors included on the branch circuits to allow for a control means for area lighting beyond local control of an individual fixture/small group of fixtures, such as an office or conference room.

In general
1. The final branch circuits to be identified and rating load to be estimated.
2. Adequate utilization/diversity Factor to be applied if applicable (depends on the application).
3. To ensure the load balance over the 3 Phase as possible.
4. For Fluorescent light fixtures arrangement of the said fixtures with respect (RYB phases) is necessary to mitigate rendering/glaring and frequency affect.
5. Then size of cable from DB to LCP can be determined/sized, rating of the protective devices can be selected and type of CB(s) subject to type of lighting fixtures.
6. Verification of Voltage drop within the prescribed limit, otherwise select the next standard cable size.

A distribution board typically has poly-phase branch breakers with the intention of feeding either other sub-panels or large loads and lighting control panel (is also one type of distribution panel) will have mostly single-pole breakers with phase-to-neutral branch circuits feeding lighting circuitry.

AQ: The basis of rating a NGR in electrical system

NGR stands for Neutral Grounding Resistor. When an earth fault current occurs on a plant, assuming that there is no external device presented to limit the earth fault current, the magnitude of the earth fault current is limited only by the earth impedance presented between the point of fault (to earth) and the return path (typically a star point of a transformer). If the earth impedance is low (type of soil being one of the reason amongst others), the fault current magnitude can be significantly high, and if left unchecked could damage the primary equipment. It is therefore mandatory that the earth fault current be limited to a suitable value, which is typically the rated value of the plant as a thumb rule. Why use the rated value? Because the plant has been designed to carry the rated current continuously.

Let’s take an example: say you have a transformer 60MVA, 132/33kV Star-Delta transformer. It is required to calculate the value of NGR to be connected to the zig-zag transformer on the 33kV Delta. the value of the resistor required to limit the earth fault current to the transformer’s LV rated value is (33 x 33) / 60 = 18.15 Ohms.

(Earth Fault current limited to rated value = (60 x 1000) / (1.732 x 33) = 1050A) When you go to a supplier you might find he supplies only 20 ohms resistor (as you might not get the exact value that you have calculated theoretically). No problem, use the 20 ohms and calculate what your new value of earth fault current would be (33 x 1000 / (1.732 x 20) = 952.6A, which is less than the transformer’s rated LV current. So you’re safe. This is how I would go about. In fact I would go a step further and introduce a safety factor of 20% i.e. I’ll bump up the value of the resistor from 20 ohms by an extra 20% and buy a resistor/ NGR of 1.2 x 20 = 24 ohms. So I am 100% sure that the earth fault current is way below the rated value and my transformer will be safe, even if the fault current goes undetected for any unforeseen reason say my earth fault protection has failed to pick up.

Make sure however that the earth fault setting that you choose is sensitive enough to pick up for the earth fault current calculated. I would generally put two relays a 64 or REF designed to pick up and operate instantly backed by a 51N with a sensitive setting but with a delay of a couple of seconds to pick up in case the 64 has failed to pick up.

So that’s it. I have described how I would go about calculating the earth fault current, selection of NGR value and how I would protect it.
Protection and related devices aiding protection don’t come cheap. Also I assume by your comment “this method is the most expensive option available since the cost of the transformer shall be astronomical”, you are referring to the Zig-Zag transformer and not the actual 132/33kV Star-Delta power transformer, under question.

I have taken a very generic example and tried to focus on how to arrive at a suitable value of an NGR, assuming an Star HV and Delta LV. My aim being to calculate how I could limit the fault current on the Delta LV. Being a Delta winding, I have to use a Zig-Zag transformer, for providing a low zero sequence path for the flow of earth fault current. It is really the Zig-Zag trafo. that bumps up the cost.

Note: If the above transformer is one of a kind, i.e. this is the only transformer in an isolated network, then I simply disregard the Zig-Zag transformer + NGR method and use the 3 PT broken delta method for 3Vo detection to drive a 59N. My cost here would be very low.

If the transformer is a Star-Star type with HV start solidly grounded, and LV star impedance (NGR) grounded, then I don’t need a Zig-Zag trafo. on the LV side. My cost is purely for the NGR alone.(Of course this transformer will have a Delta tertiary which may need it’s own protection depending on the whether one plans to load the tertiary or not. We could di

AQ: Difference between PLC and DDC system

PLC is defined as Programmable Logic Controller. It is a hardware, Includes processor, I/P & O/P Modules, Counters, Function Blocks, Timers,,, etc. The I/Os are either Analogue or Digitals or both. PLC can be configured to suit the application and to programmed in a logic manner by using one of the programing language such as Statement List, Ladder Diagram,, etc Interaction in real time between inputs and the resultant of the outputs through the program logic – PID – gives the entire Control System. While the Digital Control System I believe it is Software/ System that uses only Digital Signals for control and PLC/PC/Server/Central Unit may constitutes an Integral part of this system.

AQ: Power Transformer power losses

Power losses of ferromagnetic core depend from voltage and frequency. In case where is no-load secondary winding, power transformer has a power losses in primary winding (active and reactive power losses) which are very small, due to low current of primary winding (less than 1% of rated current) and power losses of ferromagnetic core (active and reactive power losses) which are the highest in case of rated voltage between ends of primary winding…

Of course, we can give voltage between the ends of primary winding of power transformer (voltage who is higher from rated voltage), but we need include some limits before that:

1. if we increase voltage in the primary winding of power transformer (voltage who is higher from rated voltage), we need to set down frequency, otherwise ferromagnetic core of power transformer will come in area of saturation, where are losses to high, which has a consequence warming of ferromagnetic core of power transformer and finally, has a consequence own damage,

2. if we increase voltage in the primary winding of power transformer (voltage who is higher from rated voltage), also intensity of magnetic field and magnetic induction will rise until “knee point voltage”: after that point, we can’t anymore increase magnetic induction, because ferromagnetic core is in area of saturation…

In that case, current of primary winding of power transformer is just limited by impedance of primary winding… By other side, in aspect of magnetising current, active component of this current is limited by resistance of ferromagnetic core, while is reactive component of this current limited by reactance of ferromagnetic core.

There is a finite amount of energy or power that can be handled by various ferromagnetic materials used for core material. Current increases greatly with relatively small voltage increases when you are over the knee of the magnetization curve characterized by the hysteresis loop. Nickel/steel mix materials saturate at lower flux densities than silicon steel materials. 50ni/50fe materials saturate at about 12kG; 80Ni/20Fe as low as 6kG. Vanadium Permendur material saturates at levels as high as 22kGauss- Nano-crystallines- 12.5kG (type), Ferrites -typically over 4kG at room, decreasing as temperature rises. What causes saturation?: Exceeding material limits.