Category: Blog

AQ: Compensate electric motors effect of high altitude

Case: Two electrical motors that design for altitude <1000 m but now this two electrical motor have installed on altitude 1880 m and this electrical motors become very hot. The electrical machines power is 15300KW & 9700KW and they cooled by force air and water cooler.

First – machines designed for higher-than-normal altitude (i.e. in excess of 1000 m = 3300 ft above sea level) are designed with lower allowable temperature rises. The rule-of-thumb approximation is 1 degree C for every 100 m above 1000.

This means a typical Class B rise (max 80 C over 40 C ambient) will be designed for a max 71 C rise over ambient at 1880 m altitude.

Since temperature is more-or-less proportional to the square of the current, the design either reduced in output power to limit the current, or is “overdesigned” so that the resultant output power is the effective de-rate condition. In this case, the “sea level” rating of 15300 kW would become 15300 * (71/80)^2 = 15300 * 0.94 = 14382 kW. Likewise, the 9700 kW machine would be rated for 9118 kW.

The ability to cool the machine effectively is based on two things: the amount of coolant in direct contact with the heat source(s), and the pressure of the coolant flow. At altitude, the density of the coolant is reduced significantly, hence the requirement to operate at lower power ratings. The pressure of the airflow over the windings, etc is ALSO reduced at higher altitude, making the cooling more inefficient.

Speeding up the blower (i.e. going from 6 pole speed to 4 pole speed, for example) will overcome some of this by increasing both airflow and pressure. However, the power draw on the blower drive motor may also necessitate an increase in size to accommodate the new loading parameters (including the effects of high altitude on it!). Note that if the air movement within the machine enclosure is dependent solely on the MACHINE rotor speed (i.e. a shaft mounted fan), there will be a need to develop and apply a separately-powered fan to accommodate the required changes.

The probability of voltage breakdown / corona / flashover is increased above 1800 m as well, which means at least taking a cursory look at both creepage and strike distances.

And finally – if, after all this, the machine is still overheating … time to look at the cleanliness of the liquid side of the heat exchanger. This may mean cleaning or replacing the tubing and headers, determining liquid flow rates (and pressures) and ensuring they are within original design criteria (roughly 3.8 litres per minute for each kW of loss in the rotating machine).

AQ: Soft starter settings

Reference voltage adjustment
Reference voltage is the basic condition of the equipment is able to start or not. Reference voltage adjustment requires the electric motor rotates immediately after voltage applied and the load start up. If the motor does not rotate after voltage applied, we should increase the reference voltage setting value; if the motor start speed is too fast, then reduce the reference voltage setting value. Reference voltage adjustment should be repeated for several times until the load starts immediately after voltage applied. For example, a smoke blower has a 110kW motor in debugging process with soft starter, reference voltage adjusts to 75% rated voltage, the starting current is 500A, motor start up fast; reference voltage adjusts to 40% rated voltage, motor start up in slow speed, starting current rise from 200A to 600A smoothly, and current return back after motor start is completed, therefore, it’s fully meet the soft-start requirements.

Starting time adjustment
Motor acceleration torque and starting time has direct relationship. Electronic soft starter can make the motor with voltage ramp start from initial voltage to full voltage at the set time (0.5 to 2408). Like it can reduce water impact if we extend the time of water pump flow from 0 to 100%, increase the pump speed variation time means increase the starting time which can be achieved by adjusting the starting time of the soft starter. Starting time should be adjusted according to the specific loads and repeated tests, in order to achieve smooth acceleration within starting time.

Soft stop
Soft starter allows the output voltage decreases gradually to achieve soft stop, in order to protect the equipment. Such as the impact of the water pump, when the pump stops suddenly, the water flow inertia in the pipe will raise the pipe and valves pressure suddenly and cause pipeline damaged. Soft stop to extend parking time will solve such the impact.

AQ: Frequency inverter failure analysis

Transistor frequency inverter has the following disadvantages: easy trip, difficult re-start, poor overload capacity. As the rapid development of IGBT and CPU, the inverter drive integrates perfect self-diagnosis and fault prevention features, improve the reliability greatly.

Vector control frequency inverter has “automatic torque compensation function” to overcome “starting torque inadequate” etc. This function is the inverter uses a high-speed microcomputer to calculate the torque required at current time, to modify and compensate the output voltage quickly to offset the frequency inverter output torque changed by external conditions.

In addition, because as the inverter software development more and more perfect, we can pre-set various failures parameters in the frequency inverter, to ensure continuous running after failure resolved. For example, re-start motor in free parking process; automatic reset internal failures and maintain continuous operation; adjust running curve if load torque is too high to detect the mechanical system abnormal.

AQ: Output torque of variable speed drive running above 50Hz

Generally, electric motors are designed according to 50Hz power supply, its rated torque also in this frequency. Therefore, the speed adjustment under rated frequency called constant torque speed adjustment. (T = Te, P <= Pe).

If the variable speed drive outputs frequency exceeds 50Hz, the motor torque is inversely proportional to the frequency in linear relationship decrease.
When the motor running in above 50Hz frequency, we should consider the motor loads to avoid motor lacks of torque.

For example, the motor torque is about a half in 100Hz running against 50Hz. Therefore, the speed adjustment in above rated frequency called constant power speed adjustment. (P = Ue * Ie).

As we know, for a specified motor, the rated voltage and rated current is constant.

For example, the variable speed drive and motor rated values are: 15kW/380V/30A, motors can operate at 50Hz or above.
When the frequency is 50Hz, the variable speed drive output voltage is 380V, current is 30A. Then if we increase the output frequency to 60Hz, the variable speed drive maximum voltage and current also is 380V/30A, it is obviously that the output power is fixed, so it called constant power speed adjustment, what’s the torque status now?

Since P = wT (w: angular speed, T: torque), as P keeps same, w increases, so the torque will decrease accordingly.

From another point: motor stator voltage U = E + I * R (I is the current, R is the electrical resistance, E is the EMF)
Then we can see, U and I are constant, E is constant.
And E = k * f * X, (k: constant, f: frequency, X: flux), when f changes from 50 to 60Hz, X will decrease accordingly.

For the motor, T = K * I * X, (K: constant, I: current, X: flux), so the torque T will decrease along with the flux X.

And, if the frequency is less than 50Hz, as I * R is very small, so if the U/f = E/f is constant, the magnetic flux (X) is constant, the torque is proportional to the current, which is why use the variable speed drive overcurrent capability to describe its overload (torque) capability, and known as constant torque speed adjustment (rated current is constant -> Maximum torque is constant).

Conclusion: When the variable speed drive outputs frequency increases from 50Hz, the motor outputs torque will decrease.

AQ: What is the soft stop of an electric motor?

In electric motor stop, the traditional control ways are accomplished by momentary power cutting off. But in lots of applications, it’s not allowed the motor instant shutdown. For example: high-rise buildings, building’s water pump system, it will appear huge water hammer during instant shutdown, to damage the pipe, even the pumps. To reduce and avoid “water hammer” phenomenon, the pumps motor need be shut down gradually, that is soft stop. The soft starter can meet such requirements. In pumping station, soft stop technology can avoid the pump door damaged of the pumping station, to reduce maintenance costs and maintenance works. The soft stop function in soft starter is, when the thyristor gets stop instruction, decrease conduction angle gradually from full conduction, and achieve full closed after a certain time. Stopping time can be adjusted according to actual requirements within 0 – 120s.

AQ: Avoid variable frequency drive damaged in lightning

Sometimes

AQ: Motor output torque in rotation speed (frequency) changes

Frequency power: power supplied by the power grid (commercial power).
Start-up current: frequency inverter output current in motor starts.

The motor starting torque and maximum torque by frequency inverter driving is less than direct frequency power driving.
Motor accelerates in constant frequency power supply has high impact, which can be reduced by using frequency inverter. Because there is a big starting current in motor acceleration if it’s powered by constant frequency power supply; when using frequency inverter, the inverter output voltage and frequency is increased gradually, so the motor starting current and impact is much lower.

Generally, the motor torque is decreased with frequency decreases (speed reduction). By using vector control frequency inverter, to improve output torque during motor running in low speed, and even output sufficient torque at motor low speed zones.

AQ: Soft starter energy saving principle

Induction motor is inductive load, the current lags the voltage, most electrical appliances are the same. In order to improve the power factor we need to use capacitive load for compensation, parallel capacitors or with synchronous motor for compensation. Reduce motor excitation current also can improve the power factor (HPS2 saving function, reduce excitation current by reducing voltage at light loads, to increase COS∮). Energy-saving operation mode: decrease voltage in light loads to reduce excitation current, the motor current divides into the active component and reactive component (excitation component), to increased COS∮.

Energy saving operation mode: when the motor load is light, the soft starter working at energy-saving conditions, PF switch to Y position, under the current feedback action, the soft starter reduces the motor voltage automatically, to reduce excitation component of the motor current. Thereby improving the power factor of the motor (COS∮). If the contactor in bypass state, this feature cannot works. TPF switch provides energy saving features with two reaction times: normal speed and slow speed. The soft starter operation in energy saving state automatic (In normal and slow speed), saving 40% energy in no-load and 5% with load.

AQ: Why the motor rotation speed is changeable?

r/min: motor rotation speed unit, the number of revolutions per minute, also can be expressed in rpm.
For example: 2-pole motor 50Hz 3000 r/min, 4-pole motor 50Hz 1500 r/min
Conclusion: The motor rotation speed is proportional to the frequency

Herein, the motor is induction AC motor which is used in most industries. AC induction motor rotation speed is approximate depend on the motor’s poles and frequency. As we know, the motor poles constant. Since motor poles are not continuous numbers (multiples of 2, for example, the number of poles is 2,4,6), so it’s not suitable to change this value to adjust the motor speed.

The frequency can be adjusted before supplying to the AC motor, then the motor rotation speed can be controlled freely. Therefore, motor speed controls.

n = 60f / p
n: synchronous speed
f: power frequency
p: number poles

Conclusion: change frequency and voltage is the best motor control method.

But, if just change the frequency without changing the voltage, it will occur overvoltage (over-excitation) when frequency decreases and may cause AC motor damaged. So, the voltage should be changed while the frequency inverter outputs different frequency. If the inverter output frequency exceeds rated frequency, the voltage can not continue to increase, the maximum voltage only can be equal to the motor rated voltage.
For example: In order to reduce the motor rotational speed by half, the inverter output frequency change from 50Hz to 25Hz, then the inverter output voltage should change from 400V to about 200V.

AQ: Change 230V to 460V for operating an Electric Motor

I have a generator of 3 hp, and it outputs 230 V, and I have a submersible Electric Pump, the motor of which is rated to operate at 460 V, Can I use a step up transformer to increase the voltage output from my generator and power the pump? What more parameters do I need to know of in this case?

Check to see if the generator has 3 phase power output. A typical home generator will provide 230 volt single phase output. You will not be able to step up to 460 volt and start a 3 phase motor with single phase. The only way at that point to generate 3 phase would be to use a VFD with single phase input capability and use the drive to generate 3 phase. You will still need to use a transformer. Variable frequency drives won’t normally behave well on generator power but may for an intermittent load like a submersible pump.