Category: Blog

AQ: VFD Kinetic Buffering and Flying restart

Voltage Loss ride through with flying restart:
In this method, when the voltage sag causes the variable frequency drive to reach its undervoltage trip level, the VFD drive will shut off the inverter section and thus remove power from the motor instead of tripping. The motor will coast down during the duration of the sag and, as soon as the voltage recovers, the VFD will start into the still-spinning motor and ramp up to set speed. How much the motor speed will drop depends on the inertia of the load and the duration of the sag.
You have to configure the VFD for flying restart. During low input voltage the inverter section is cut off to maintain the DC bus voltage. If the voltage restores before the DC bus voltage goes below the tripping value, the inverter is again put on but the driven load speed has already reduced due to brief period of no voltage at the motor terminal. Flying restart feature enables the variable frequency drive to restart the Motor at the same speed at which the motor is operating thus preventing any high current. So it is basically catching a spinning motor. Without flying restart high current will be observed once the inverter section is put ON. Flying restart feature is also helpful if you want to restart a motor which is already spinning.

Kinetic backup
This option, which is also provided by some variable frequency drive manufacturers, uses the energy stored in the mechanical load to keep the DC bus voltage from dropping down to the trip level. This is accomplished by running the inverter section during a voltage sag at a frequency slightly below the motor frequency, causing the motor to act as a generator. Similar to the flying restart option, the motor speed will drop while it is acting as a generator, however the advantage is that the motor is never disconnected from the drive. This option works best for those high-inertia loads.
Kinetic buffering is a feature to prevent the variable frequency drive from tripping during voltage sags. If the VFD trips due to DC bus undervoltage there is no need for kinetic buffering.

AQ: Transformer harmonics

The harmonics are created by the loads that the transformer supplies power to. If your loads include a high percentage of electronic loads like IT equipment, electronic ballast lighting, electronic motor controls, etc., there can be a very high amount of harmonics that circulate back to the transformer. The harmonics create an increase in the neutral currents. Most standard transformers are not designed to handle the higher harmonics and corresponding high temperature. Type K rated transformers are designed withstand the higher harmonics, without derating the transformer or limiting its maximum load. There are harmonics filters on the market as well as the use of isolation transformers.

B/H curve of the magnetic material forming the transformer core is not linear, so if a sinusoidal voltage is being applied for a sinusoidal current (and hence sinusoidal flux & a sinusoidal secondary voltage), the magnetizing current is not sinusoidal. Thus the magnetizing current of a transformer having an applied sinusoidal voltage will comprise a fundamental component and various harmonics. The magnitude and composition of these harmonics will depend on the magnetizing characteristic of the core material and the value of the peak flux density.

By the way:
– The standard Transformer “Non-saturated” generate Harmonics only in transient case when the power is supplied, and after this too small time it doesn’t generate any kind of Harmonics
– The Transformer generates Harmonics if it’s saturated
– We should take care when selecting the Transformer’s Power if there are a lot of installed Non-linear Loads, so for this case, we can select the power after define the correction factor by using the special curve done by “IEC”, or calculating this factor by using a special Formula done by “UTE – France”.

All AC signals are sinusoidal and periodic. These periodic signals can be resolved into a kind of trigonometric series – fourier series which is a summation of a fundamental and multiples of fundamental frequency.

The moment there is slight distortion from sinusoidal nature , it leads to harmonics in addition to the fundamental signal.. One way is to use DC signals… no harmonics.

As long as the AC signal is perfect sinusoidal , load & source is linear, there will be no harmonics. The way to get rid of harmonics is to have perfect source and perfect loads.

The non linearity introduced due to energy storing magnetic circuits, switching circuits, energy converting & inverting circuits distort the waveform to non sinusoidal. Therefore leads to harmonics. .

The way, there are antibiotic medicines for diseases. One needs to install the filter devices, which produce counter currents to suppress the effects of harmonics. The filters contain capacitors, inductors & power electronic components which are switched in anti-phase to harmonics producing elements. Thereby absorb harmonics.

AQ: Charging Power transformer through lower rated grid auto Transformer

AQ: Frequent tripping in Unit Station Transformer

We are facing problem of frequent tripping in Unit Station Transformer -2 during heavy rain. During checking, not found any abnormalities
1. Fault UST2 OTI Trip Observation- * Direct OTI trip initiated without Alarm
* Oil temperature is normal
* Tripping contacts are not physically operated
* OTI trip contacts are operated frequently as per in Disturbance record Action taken-Spare Core of another cable used for OTI Trip contact

2. UST2 PRD Trip
* PRV contacts are not physically operated
* PRV trip contacts are operated frequently as per in Disturbance record New cable used for all contacts

Make sure for rainy conditions the marshalling box is properly closed and weather protected as moist condition also leads to tracking and may simulate tripping inadvertently. Please also make sure the tripping impulse from OTT/WTT/BT/MOG/PRD etc are driving a mechanical hand reset type VAJH type relay and the output contacts of this relays are used for trip ckt initiation.
If these are substituted by numerical relay binary inputs then also there will be a problem of spurious tripping.

Make sure the grounding of the multicore control cable if sheathed the grounding should be at TRPP panel end only, if armoured cable is used the armour grounding at the panel end only.’

I am assuming that the trip circuit is floating DC (ungrounded). If so, the moisture could be causing a “sneak” circuit, otherwise known as a “hot short” in the tripping circuit, which essentially bypasses the sensing relay contacts and actuates the tripping relay coil. I would check the cabling between the sensing relay contacts and the trip relay coil and the cabling on the hot side of the sensing relay contacts for insulation problems.

AQ: Pressure switch on three phase motor

Q: Is there a way of connecting a three phase pressure control switch on a three phase motor. Also is there a three phase float switch for a three phase submersible pump i know of a single phase switch.

A: The switch only needs to have a single contact since you use a three-phase motor controller to operate the motor. The switch is wired into the low voltage contactor coil circuit to turn the motor on and off.

You can connect a pressure switch for the purpose of motor control on its low level pressure or high level pressure. It is advisable to utilize pressure switch on the control cct, and connect the contactor coils through the auxiliary NC/NO contacts depending on whether you are interested on low pressure or high pressure control. It is not good practice to allow power cct through control ccts. You don’t need a 3 phase float switch to achieve controls of a 3phase submersible pump. You should be interested in the auxiliary terminals which will allow control flexibility for low level and upper level control. A single phase float switch will give you desired result. If you are controlling more than 1 no. 3phase motors located at different places from the same pressure signal, then your 3 phase pressure switch can be employed to control the different motors separately. In addition, some terminals could be used for indication/annunciation purposes. However, a single phase pressure switch can give you all the controls you need for a 3phase motor.

AQ: “Hissing sound” in SF 6 Gas insulated HV Switch Gear

This could be internal corona discharge. The switchgear should be de-energized and closely examined. That means pump out the SF6 and take it apart. Examine all insulating components.

Especially if the sound can be localized to portions of the switchgear which do not have bushings for connection to overhead lines. Even if the sound is in the area of air bushings, deenergizing will allow more in-depth inspection and addressing any sharp edges or cracked insulators, etc.

Take this pieces of equipment out of service immediately, perform a “hi-pot” or high potential test on the various elements of the switchgear and attempt to locate the area that is “leaking” to ground (or between phases). Inspect closely for indications of tracking on insulators from corona discharge and replace any compromised components. After component replacement, installation of new SF6 gas and other repairs, re-run the Hi-Pot test to confirm that the switchgear is able to withstand voltages at least 50% greater than the name-plate rating. Of course all of this advice is worthless if the unit has already failed.

Remember that a Hi-pot is actually a destructive test. It challenges the insulation to the point of breakdown. Check the vendor recommendations before you Hi-pot equipment that has been in-service.

AQ: Variable frequency drive Constant Torque/Variable Torque

A typical variable torque application would be a centrifugal pump. A typical constant torque application would be a conveyor, and there are positive displacement pumps that are also constant torque. Have a talk with a mechanical engineer, get them to show you curves and explain.

DBR stands for Dynamic braking resistor. Regeneration will happen when the motor rotates a speed higher than the speed which corresponds to the frequency setpoint ie.. the rotor speed is more than the speed of the rotating magnetic field.
Regeneration feeds back energy to the drive which results in DC bus overvoltage. To prevent the drive from tripping due to DC bus overvoltage the DBRs are used. The regenerative energy is discharged in the resistor as heat.

Regenerative Breaking – we used to have VFD on a vehicle rolling road. So when the car is travelling faster than the VFD, the VFD generate back into the power supply – causing a break effect. If you had a large mass- large inertia that you want to stop quickly, you need to break the load- you can do that with regenerative breaking. Otherwise, disconnecting the variable frequency drive, will mean your load just freely rotates, and that can mean it will take 30 minute to come to a stop for a large inertia.

Active Front end- I first came across this term with ABB. It is all to do with how to mitigate harmonics from VFDs. You can use phase shift transformers, but with modern electronics, you can use a opposite phase current to counter act the harmonics generated from the VFD. So the overall impact on the network is small.
In active front end technology the rectifier is basically an inverter with IGBTs.
The main advantage are:
1) Low current THD <5 %
2) It is basically a four quadrant rectifier .Referring my last post please note that you will not require a DBR with AFE. The increase in voltage of DC Bus due to regeneration can be fed back to the input AC supply in the form of energy. So you don’t require a DBR.
3) AFE drives have very good immunity to input voltage fluctuations.

Just an advice. Please go through variable frequency drive literatures (available in plenty) to have a good understanding of the different VFD technologies.
Selection of VFD requires proper understanding of the VFDs and the overall electrical system. There are lots of marketing gimmicks in the world of VFD. Always be careful before selecting a VFD specially higher KW drives.

For large drives, you need to speak with supplier to configure your machine correctly. There are many options, but yes active front ends are available. But there are other solutions; ASI Robicon use a current driven VFD, so harmonics are lessened in the first place, so an active front end is not the right terminology. It is a different solution. I used a 10MW version of that type of ac drive. I think Siemens have bought the company since.

AQ: Motor power cable – bigger or smaller?

When a choosing a power cable for a motor, we prefer using one larger diameter cable than two smaller diameter cables in parallel, although it would cost less to do so. Why?

1. Conductors/Cables/Feeders in parallel connection generally are not recommended unless there is no option, therefore it can be adopted under the following conditions:
i. Cables are of the same material and cross section area.
ii. Are of the same route and length.
iii. The sum of the current carring capacity of the parallel circuits after applying all necessary applicable correction factors should be greater than the nominal regulated current of the protective device.
iv. The current carrying capacity (before derating) shall be not less than 300A (according to the local authority/Service provider requirement/regulation).
v. Capability of addressing the Thermal & electrodynamics constraints in proper way.

2. Some designs call for parallel connection so as to:
i. Overcome the voltage drop.
ii. Avoid the difficulties of installing big size cables (bending, pulling) due corridor limitation,etc.
iii. Meet the Power demand.
iv. Mitigate the cost (Costwise).

3. For electrical Motors, two connections are normally required. One from MDB to Motor CP and other from CP to the Motor.
By virtue of the requirement of Delta/star starter, two cables are required (Mandatory) between CP & motor (one will be dead just after changing to delta connection).
While the connection from the MDB to CP will be one, sized according to the Motor rating.

However, Parallel connection of Feeders need an expert engineer(s) to meet the requirement since Short Circuit fault protection for parallel circuits require further evaluation from the Engineer that the impact of the short circuit current within the parallel section will have severe fault due to fault current path that can occur in addition subtransient contribution of the downstream system.

AQ: Change transformer vector group

Transformer nameplate vector group is YNd1. However, the nature of connection on both its primary and secondary side is such that:
Generator phase A = Transformer phase c
Generator phase B = Transformer phase b
Generator phase C = Transformer phase a

Also, on transformer HV (secondary connected to grid),
Transformer phase A = Grid phase C
Transformer phase B = Grid phase B
Transformer phase C = Grid phase A

The questions are:

1. How does this affect the vector group (YNd1) of the transformer? Will it be changed to YNd11?
2. Will it make any difference as far as the vector group is concerned if instead of phase A and C, phase B and C were swapped on both ends of the transformer?
3. The transformer protection relay is configured for YNd1 group, and it is reading negative phase sequence current (ACB instead of ABC). Changing the vector group configuration will solve the problem?
4. Relay is used for differential protection (percentage differential) of the transformer.
Will this negative phase sequence affect normal operation of the transformer in any way?

1. How does this affect the vector group (YNd1) of the transformer? Will it be changed to YNd11?

Yes, the name plate vector group of a transformer is only valid for a standard phase rotation ABC. for a phase rotation ACB the apparent vector group will be YNd11.

2. Will it make any difference as far as the vector group is concerned if instead of phase A and C, phase B and C were swapped on both ends of the transformer?

No, by swapping any two phases the rotation becomes no standard and the apparent vector group will become YNd1

3. The transformer protection relay is configured for YNd1 group, and it is reading negative phase sequence current (ACB instead of ABC). Changing the vector group configuration will solve the problem?

I think the way the relay is configured at the moment will give you problems, if I’m correct you should be able to see differential current when the transformer is loaded, and it is likely to trip on the first through fault (can you confirm this). To resolve this issue you have two options.
i) Set the vector group to YNd11 in the relay, this will remove the differential current but will mean the relays see’s 100% NPS current and 0% PPS current, this may give you problem if you have any NPS elements enabled in the relay ( inter turn fault detection, directional elements etc)
ii)Set the vector group to YNd1 and the phase rotation setting to non standard ACB this will get rid of the NPS currents and the differential current, so this is probably the best solution.

4. Relay is used for differential protection (percentage differential) of the transformer.
Will this negative phase sequence affect normal operation of the transformer in any way?

No, there will be no problem with the transformer itself just the relay protecting it.

As i said previously if I’m understanding the problem correctly, you should be able to see differential current at the moment when the transformer is loaded, is this correct?

AQ: Transformer tap changer

Q:
We are frequently changing tap position of Unit station transformer due to voltage problem. What are the impacts on transformer life and is there any solution to minimize this?

A:
Having more tap changing per week is not bad, but it wears out the tap changer faster and does require more maintenance. We set our bandwidth at 1.5 volts, 0.75 up and 0.75 down, with a minimum timer of 30 seconds (voltage has to be out of bandwidth for more than 30 seconds for tap changer to move). Voltage for the OLTC controller is based on a 120V base. This normally worked well for our city loads, but perhaps your loads vary even more. I have used a bandwidth of 2 volts maximum with good success to keep the OLTC from tapping more than I liked (250 taps per week, and naturally if your loads swing more than what we had then your taps per week are going to be higher). The 250 count per week maximum is just a goal we set to try and maximize the life of our tap changers and minimize our maintenance. Looking at your timer and bandwidth may help reduce the taps per week. When the tap count per week jumps up suddenly you can suspect the controller might be bad. One more thing, I never use the X setting, just the R. I would draw the voltage “curve” versus the current and figure out my maximum voltage based on the maximum current. This worked well for me for my 23 years of utility work (again, these are city loads, base power factor during the summer was 85%). The power factor would be higher in the winter and lower in the summer (summer at 85% and winter was over 95% because in the winter we had no air conditioning loads). That is why I did not use the X setting (one setting year round).

Since it appears that you are talking about OLTC, then 250 taps per week is the maximum level that is reasonable in my opinion for a transformer serving varying loads, such as a city. I worked for electric utilities in the US for 23 years and looked at load tap changing counts every week for over 450 MW of transformers (15 MVA to 46 MVA all serving city loads). This count is the top end we would allow. The average count was in the 125-150 range per week (summer loads, with wide varying loads each day, winter loads caused less tapping per week). Oil does not degrade rapidly in the OLTC (that is operating properly) even with a maximum of 250 counts per week, but we would take oil samples every year of the OLTC and the transformer to keep tabs on their overall health. If the oil in the OLTC does degrade rapidly, then there is a good chance that the alignment of the taps is improper and arcing may be occurring during the tap changing.

OLTC has little or no effect on the life of the transformer. Also, there are two separate oil compartments, one for the OLTC and one for the transformer.