AQ: VFD overcurrent trip during acceleration/deceleration

First, we should know it’s caused by loads or itself. If it’s the variable frequency drive problem, we can check the trip current from the VFD operation history, to see if the current exceeds the VFDs rated current or electronic thermal relay settings value. If three-phase voltages and currents are balanced, we should consider overload or sudden change situations, such as motor stall. If the load inertia is big, we should extend the acceleration time appropriately, this is suitable for a good VFD. If the trip current is within the variable frequency drive rated current or electronic thermal relay setting range, then it maybe the IPM module or relevant parts failure. In this case, we can measure the variable frequency drive output terminals (U, V, W), and resistance of the P, N terminals on DC side to determine whether the IPM module damaged or not. If the module is good, then we can know it is the drive circuit trouble. If IPM module overcurrent or ground wire short circuit causes the VFD trip in deceleration, generally it’s the top half-bridge module or drive circuit fault; If IPM module overcurrent during acceleration, then it is the next half-bridge module or drive part fault. For such failures, mostly it’s the external dust entering the variable frequency drives or environment moisture.

ABBdriveX